- DIN series
-> 45 W Single Output DIN Rail Power
-> 75 W Single Output DIN Rail Power
-> 120 W Single Output DIN Rail Power
-> 240 W Single Output DIN Rail Power
-> 480 W Single Output with PFC Function
-> 480 W Single Output with PFC Function 2
-> 240W Three Phase DIN Rail Power
-> 480W Three Phase DIN Rail Power

Universal AC input / Full range
UL508 listed
Installed on DIN rail TS35 / 7.5 or 15
Protections : Short circuit / Over load / Over voltage / Over temp.
Fixed switching frequency at 100 KHz
Approvals : UL / CUL / TUV / CB / CE
LED indicator for power on
Cooling by free air convection
100% full load burn-in test
3 years warranty
AC input voltage range . . . . . .85~234VAC; 120~370VDC
AC inrush current. . . . . . . . .Cold start, 30A at 115VAC, 60A at 230VAC
DC adjustment range. . . . . . . .±10% rated output voltage
Over load protection . . . . . . .105%~150% constant current limiting, auto-recovery
Over voltage protection. . . . . .115%~135% rated output voltage
Setup, rise, hold up time. . . . .800ms, 60ms, 50ms at full load and 230VAC
Withstand voltage. . . . . . . . .I/P-O/P:3KVAC, I/P-FG:1.5KVAC, 1minute
Working temperature. . . . . . . .0~45°C@100%, -10°C@80%, 50°C@80% load
Safety standards . . . . . . . . .UL508, TUV EN60950 approved
EMC standards. . . . . . . . . . .EN55022 class B, EN61000-3-2,-3
EN61000-6-2, EN61000-4-2,3,4,5,6,8,11, ENV50204
Connection . . . . . . . . . . . .I/P:3 poles, O/P:4 poles screw DIN terminal
Packing. . . . . . . . . . . . . .0.31kg; 48pcs / 16.1kg / 1.3CUFT
Stock No. |
Model No. |
Output |
Tol. |
R&N |
Effi. |
10441 |
DR-4505 |
5V, 0~5.0A |
±2% |
100mV |
72% |
10442 |
DR-4512 |
12V, 0~3.5A |
±1% |
200mV |
77% |
10443 |
DR-4515 |
15V,0~2.8A |
±1% |
240mV |
77% |
10444 |
DR-4524 |
24V, 0~2.0A |
±1% |
480mV |
80% |

Universal AC input / Full range
UL508 listed
Installed on DIN rail TS35 / 7.5 or 15
Protections : Short circuit / Over load / Over voltage / Over temp.
Fixed switching frequency at 50 KHz
Approvals : UL / CUL / TUV / CB / CE
LED indicator for power on
Cooling by free air convection
100% full load burn-in test
3 years warranty
AC input voltage range . . . . . .85~264VAC; 120~370VDC
AC inrush current. . . . . . . . .Cold start, 30A at 115VAC, 60A at 230VAC
DC adjustment range. . . . . . . .12V: 12~14V, 24V: 24~28V, 48V: 48~53V
Over load protection . . . . . . .105%~150% constant current limiting, auto-recovery
Over voltage protection. . . . . .121%~142% rated output voltage
Setup, rise, hold up time. . . . .1000ms, 60ms, 50ms at full load and 230VAC
Withstand voltage. . . . . . . . .I/P-O/P:3KVAC, I/P-FG:1.5KVAC, 1minute
Working temperature. . . . . . . .-10~60°C (refer to output derating curve)
Safety standards . . . . . . . . .UL508, TUV EN60950 approved
EMC standards. . . . . . . . . . .EN55022 class B, EN61000-3-2,-3
EN61000-6-2, EN61000-4-2,3,4,5,6,8,11, ENV50204
Connection . . . . . . . . . . . .I/P:3 poles, O/P:4 poles screw DIN terminal
Packing. . . . . . . . . . . . . .0.6kg; 20pcs / 13.0kg / 1.1CUFT
Stock No. |
Model No. |
Output |
Tol. |
R&N |
Effi. |
10531 |
DR-75-12 |
12V, 0~6.3A |
±2% |
100mV |
76% |
10532 |
DR-75-24 |
24V, 0~3.2A |
±1% |
150mV |
80% |
10533 |
DR-75-48 |
48V,0~1.6A |
±1% |
240mV |
81% |

AC input selectable by switch
UL508 listed
Installed on DIN rail TS35 / 7.5 or 15
Protections : Short circuit / Over load / Over voltage / Over temp.
Fixed switching frequency at 55 KHz
Approvals : UL / CUL / TUV / CB / CE
LED indicator for power on
Cooling by free air convection
100% full load burn-in test
3 years warranty
AC input voltage range . . . . . .88~132VAC/ 176~264VAC selectable by switch
AC inrush current. . . . . . . . .Cold start, 30A at 115VAC, 60A at 230VAC
DC adjustment range. . . . . . . .12V: 12~14V, 24V: 24~28V, 48V: 48~53V
Over load protection . . . . . . .105%~150% constant current limiting, auto-recovery
Over voltage protection. . . . . .120%~140% rated output voltage
Setup, rise, hold up time. . . . .500ms, 70ms, 30ms at full load and 230VAC
Withstand voltage. . . . . . . . .I/P-O/P:3KVAC, I/P-FG:1.5KVAC, 1minute
Working temperature. . . . . . . .-10~60°C (refer to output derating curve)
Safety standards . . . . . . . . .UL508, UL60950-1, TUV EN60950 approved
EMC standards. . . . . . . . . . .EN55022 class B, EN61000-3-2,-3
EN61000-6-2, EN61000-4-2,3,4,5,6,8,11, ENV50204
Connection . . . . . . . . . . . .I/P:3 poles, O/P:4 poles screw DIN terminal
Packing. . . . . . . . . . . . . .0.79kg; 20pcs / 16.5kg / 1.1CUFT
Stock No. |
Model No. |
Output |
Tol. |
R&N |
Effi. |
10541 |
DR-120-12 |
12V, 0~10A |
±2% |
80mV |
80% |
10542 |
DR-120-24 |
24V, 0~5.0A |
±1% |
80mV |
84% |
10543 |
DR-120-48 |
48V,0~2.5A |
±1% |
100mV |
85% |

Universal AC input / Full range
UL508 listed
PF>0.98@115VAC, >0.95@230VAC
Installed on DIN rail TS35 / 7.5 or 15
Protections : Short circuit / Over load / Over voltage / Over temp.
Fixed switching frequency at 100 KHz
Approvals : UL / CUL / TUV / CB / CE
LED indicator for power on
Cooling by free air convection
100% full load burn-in test
3 years warranty
AC input voltage range . . . . . .85~264VAC; 120~370VDC
AC inrush current. . . . . . . . .Cold start, 30A at 115VAC, 50A at 230VAC
DC adjustment range. . . . . . . .24~48V for 24V model, 48~53V for 48V model
Over load protection . . . . . . .105%~150% constant current limiting, auto-recovery
Over voltage protection. . . . . .30~36V for 24V model, 54~60V for 48V model
Setup, rise, hold up time. . . . .800ms, 40ms, 20ms at full load and 230VAC
Withstand voltage. . . . . . . . .I/P-O/P:3KVAC, I/P-FG:1.5KVAC, 1minute
Working temperature. . . . . . . .-10~55°C@100%, 70°C@60% load
Safety standards . . . . . . . . .UL508, UL60950-1, TUV EN60950 approved
EMC standards. . . . . . . . . . .EN55022 class B, EN61000-3-2,-3
EN61000-6-2, EN61000-4-2,3,4,5,6,8,11, ENV50204
Connection . . . . . . . . . . . .I/P:3 poles, O/P:4 poles screw DIN terminal
Packing. . . . . . . . . . . . . .1.2kg; 12pcs / 15.5kg / 1.2CUFT
Stock No. |
Model No. |
Output |
Tol. |
R&N |
Effi. |
10551 |
DRP-240-24 |
24V, 0~10A |
±1% |
80mV |
84% |
10552 |
DRP-240-48 |
48V, 0~5.0A |
±1% |
150mV |
85% |

AC input 180~264V only
UL508 listed
Installed on DIN rail TS35 / 7.5 or 15
With passive PFC function compliance to EN61000-3-2
Protections : Short circuit / Over load / Over voltage / Over temp.
89% high efficiency
EN61000-6-2 (EN50082-2) industrial immunity level
Cooling by free air convection
3 years warranty
AC input voltage range . . . . . .180~264VAC; 250~370VDC
AC inrush current. . . . . . . . .Cold start, 50A at 230VAC
DC adjustment range. . . . . . . .24~48V for 24V model, 48~53V for 48V model
Over load protection . . . . . . .105%~150% constant current limiting, auto-recovery
Over voltage protection. . . . . .30~36V for 24V model, 54~60V for 48V model
Setup, rise, hold up time. . . . .1200ms, 40ms, 16ms at full load and 230VAC
Withstand voltage. . . . . . . . .I/P-O/P:3KVAC, I/P-FG:1.5KVAC, 1minute
Working temperature. . . . . . . .-20~50°C@100%, 70°C@60% load
Safety standards . . . . . . . . .UL508, TUV EN60950 approved
EMC standards. . . . . . . . . . .EN55022 class B, EN61000-3-2,-3
EN61000-6-2, EN61000-4-2,3,4,5,6,8,11, ENV50204
Connection . . . . . . . . . . . .I/P:3 poles, O/P:4 poles screw DIN terminal
Packing. . . . . . . . . . . . . .2.1kg; 6pcs / 13.6kg / 1.75CUFT
Stock No. |
Model No. |
Output |
Tol. |
R&N |
Effi. |
10693 |
DRP-480-24 |
24V, 0~20A |
±1% |
120mV |
89% |
10694 |
DRP-480-48 |
48V, 0~10A |
±1% |
120mV |
89% |

AC input 115/230 selectable by switch
UL508 listed
Installed on DIN rail TS35 / 7.5 or 15
With passive PFC function compliance to EN61000-3-2 (230Vin only)
Protections : Short circuit / Over load / Over voltage / Over temp.
89% high efficiency
EN61000-6-2 (EN50082-2) industrial immunity level
Cooling by free air convection
3 years warranty
AC input voltage range . . . . . .90~132VAC/ 180~264VAC selectable by switch
AC inrush current. . . . . . . . .Cold start, 50A at 230VAC
DC adjustment range. . . . . . . .24~48V for 24V model, 48~55V for 48V model
Over load protection . . . . . . .105%~150% constant current limiting, auto-recovery
Over voltage protection. . . . . .30~36V for 24V model, 54~66V for 48V model
Setup, rise, hold up time. . . . .1200ms, 40ms, 16ms at full load and 230VAC
Withstand voltage. . . . . . . . .I/P-O/P:3KVAC, I/P-FG:1.5KVAC, 1minute
Working temperature. . . . . . . .-20~50°C@100%, 70°C@60% load
Safety standards . . . . . . . . .UL508, TUV EN60950-1 approved
EMC standards. . . . . . . . . . .EN55022 class B, EN61000-3-2,-3
EN61000-6-2, EN61000-4-2,3,4,5,6,8,11, ENV50204
Connection . . . . . . . . . . . .I/P:3 poles, O/P:4 poles screw DIN terminal
Packing. . . . . . . . . . . . . .2.1kg; 6pcs / 13.6kg / 1.75CUFT
Stock No. |
Model No. |
Output |
Tol. |
R&N |
Effi. |
10931 |
DRP-480S-24 |
24V, 0~20A |
±1% |
120mV |
89% |
10932 |
DRP-480S-48 |
48V, 0~10A |
±1% |
120mV |
89% |

Input 340~550VAC, 3-phase 4 wires
High efficiency and low dissipation
Protections : Short circuit / Over load / Over voltage / Over temp.
Installed on DIN rail TS35 / 7.5 or 15
EN61000-6-2 industrial immunity level
100% full load burn-in test
UL / CUL / TUV / CB / CE pending
Cooling by free air convection
3 years warranty
AC input voltage range . . . . . .340~550VAC, 3-phase 4 wires (dual-phase operation possible)
AC inrush current. . . . . . . . .Cold start, 50A
DC adjustment range. . . . . . . .24V: 24~48V, 48V: 48~55V
Over load protection . . . . . . .105%~150% constant current, auto-recovery
Over voltage protection. . . . . .24V: 30~36V, 48V: 59~66V
Over temp. protection. . . . . . .Shut down output voltage, recovers automatically after temperature goes down
Withstand voltage. . . . . . . . .I/P-O/P:3KVAC, I/P-FG:1.5KVAC, 1minute
Working temperature. . . . . . . .-20~+70°C, please refer to derating curves
Safety standards . . . . . . . . .UL508, TUV EN60950-1 approved
EMC standards. . . . . . . . . . .EN55022 class B, EN61000-3-2,3, ENV50204
EN61000-4-2,3,4,5,6,8,11, EN61000-6-2
Connection . . . . . . . . . . . .I/P:4 poles, O/P:4 poles screw DIN terminal
Packing. . . . . . . . . . . . . .1.1kg; 12pcs / 14.3kg / 1.2CUFT
Stock No. |
Model No. |
Output |
Tol. |
R&N |
Effi. |
10941 |
DRT-240-24 |
24V, 0~10A |
±1% |
80mV |
89% |
10942 |
DRT-240-48 |
48V, 0~5.0A |
±1% |
80mV |
88% |

Input 340~550VAC, 3-phase 4 wires
High efficiency up to 90%
Protections : Short circuit / Over load / Over voltage / Over temp.
Installed on DIN rail TS35 / 7.5 or 15
EN61000-6-2 industrial immunity level
100% full load burn-in test
UL / CUL / TUV / CB / CE pending
Cooling by free air convection
3 years warranty
AC input voltage range . . . . . .340~550VAC, 3-phase 4 wires (dual-phase operation possible)
AC inrush current. . . . . . . . .Cold start, 50A
DC adjustment range. . . . . . . .24V: 24~48V, 48V: 48~55V
Over load protection . . . . . . .105%~150% rated output power; Constant current limiting, auto recovery
Over voltage protection. . . . . .24V: 30~36V, 48V: 59~66V shut off, AC recycle to re-start
Over temp. protection. . . . . . .Shut down output voltage, recovers automatically after temperature goes down
Withstand voltage. . . . . . . . .I/P-O/P:3KVAC, I/P-FG:1.5KVAC, O/P-FG:0.5KVAC, 1minute
Working temperature. . . . . . . .-20~+70°C, please refer to derating curves
Safety standards . . . . . . . . .UL508, TUV EN60950-1 approved
EMC standards. . . . . . . . . . .EN55022 class B, EN61000-3-2,3, ENV50204
EN61000-4-2,3,4,5,6,8,11, EN61000-6-2 heavy industry level
Connection . . . . . . . . . . . .I/P:4 poles, O/P:4 poles screw DIN terminal
Packing. . . . . . . . . . . . . .2.2kg; 6pcs / 14.2kg / 1.75CUFT
Stock No. |
Model No. |
Output |
Tol. |
R&N |
Effi. |
10951 |
DRT-480-24 |
24V, 0~20A |
±1% |
80mV |
89% |
10952 |
DRT-480-48 |
48V, 0~10A |
±1% |
80mV |
90% |